The nut module implements the health check "nutups" checking
remote or local uninterruptible power supplies monitored by
the Network UPS Tools (http://www.networkupstools.org/).

The module requires NUT >=1.4 to be installed. 

SYNTAX

(please use the testers command in order to get an up-to-date
syntax description)

nutups


  chargefail: percentage
    Battery Charge Fail level - Big Sister panics (red) if
    battery charge goes below this level (default: 30%)

  chargewarn: percentage
    Battery Charge Warn level - Big Sister warns (yellow) if
    battery charge goes below this level (default: 90%)

  runtimefail: percentage
    Battery Runtime Fail level - Big Sister panics (red) if UPS
    runtime goes below this level (default: 360)

  runtimewarn: percentage
    Battery Runtime Warn level - Big Sister warns (yellow) if UPS
    runtime goes below this level (default: 600)

  loadfail: percentage
    Battery Load Fail level - Big Sister panics (red) if UPS
    load goes above this level (default: 95%)

  loadwarn: percentage
    Battery Load Warn level - Big Sister warns (yellow) if UPS
    load goes above this level (default: 85%)

  status: string
    Normal Status - Big Sister will warn (yellow) if status of
    the UPS does not equal this status (default: OL)

  ups: list of regular expression/string
    A list of UPS names

  perf: integer number
    report perf data every perf minutes

  item: string
    Item as which to report.

